FTS .FGI 0.01% class fluxgate high-precision current sensor

Used for high-precision DC, AC, and pulse current measurement, with optimal measurement accuracy up to 0.01% 。

Features

application

Advantages

standard

l   High-precision zero-flux closed-loop control

l   Strong resistance to electromagnetic interference

l   LED status display

l   Full-range automatic switching technology

l   Wide temperature range design, operating temperature from -40 to 90

l   Smart grid, new energy

l   Industrial manufacturing, converters, inverters

l   Aerospace , satellites, rockets

l   Verification and Calibration Equipment

l   High-speed trains, subways, and trolleybuses

l   Original and secondary border isolation measurement

l   0.01% level measurement accuracy

l   Excellent linearity and extremely low temperature drift.

l   Wide bandwidth and low response time

l   Professional magnetoelectric design, strong resistance to electromagnetic interference

l   Excellent testing capabilities

l   IEC 61010-1

l   IEC 61000-6-2:2016

l   IEC 61000-6-3:2006

l   IEC 61010-2-030:2017

l   IEC 60112

 

 

 

 

 

Environmental and mechanical properties

project

parameter

Ambient operating temperature / T A

-40 to 90

Storage ambient temperature / T S

-40 to 90

Relative humidity /RH

20%RH to 80%RH

mechanical shock protection level

IP54

 

Insulation properties

project

Test conditions

parameter

Isolation voltage / V d

50Hz, 1min

5kV

Transient isolation withstand voltage / V w

50us

10kV

Creepage distance / d Cp

 

11mm

Electrical clearance distance / d Ci

 

11mm

Compared to the tracking index / CTI

IEC-60112

600V

 

Electrical parameters

project

Test conditions

Minimum value

nominal value

Maximum value

unit

Operating voltage / V C

±14.2

±15

±15.8

V

Static power consumption current / I PWR

Primary rated current

±30

mA

Accuracy / X G

Input DC, 25±10ºC

0.01

%

Linearity / ε L

10

ppm

Dynamic response time / t r

di/dt = 100 A/μs, rising to 90% IPN

1

μs

Rate of change of current / di / dt

2 00

A/μs

Bandwidth (-3dB)/F

0

1 00

kHz

Zero-point offset current / I<sub> OT</sub>

Full temperature range

±5

μA

Temperature stability / X G

 

 

50

ppm/K

 

Selection list

0 to ±200A Selection List 1

model

FGI30

FGI50

FGI60

FGI100

FGI200

Primary side rated DC/I DC

±30A

±50A

± 60A

±10 0A

±200A

Primary side rated AC RMS value / I AC

21 A

35A

42A

70A

141A

Primary overload current / IPM

±42A

±60A

± 72A

± 120A

± 240A

Transformation ratio ( primary side: secondary side ) I KN

600:1

1000:1

600:1

1000:1

1000:1

Rated output current / I S N

50mA​

50mA​

100mA

100mA

200mA​

Measuring resistance

20Ω

20Ω

20Ω

20Ω

10Ω

Installation method

Disc installation

aperture

20mm

External structure

Figure 1

 

 

±300 to ±700A Selection List 2

model

FGI300

FGI400

FGI500

FGI600

FGI700

Primary side rated DC/I DC

±30 0A

±40 0A

± 500A

± 600A

± 700A

Primary side rated AC RMS value / I AC

212A

282A

353A

424A

495A

Primary overload current / IPM

± 360A

± 480A

± 600A

± 720A

± 840A

Transformation ratio ( primary side: secondary side ) I KN

1 000:1

1 000:1

1 0 00: 1

1 0 00: 1

1,000 : 1

Rated output current / I S N

30 0mA

400mA​

500 mA

600mA​

700mA​

Measuring resistance

10Ω

5Ω

3Ω

2Ω

2Ω

Installation method

Disc installation

aperture

35mm/45mm

External structure

Figure 2/Figure 3

 

External dimensions and specifications

Figure 1: Outline drawing of 0 to ±200A current sensor

Figure 2: Outline drawing of ±300 to ±700A current sensor

Figure 2: Outline drawing of ±300 to ±700A current sensor

Figure 3: Outline drawing of ±800A to ±1500A current sensor

Figure 3: Outline drawing of ±800A to ±1500A current sensor

Figure 4: Outline drawing of ±1500 to ±2500A current sensor