FTS .FGR 0.2% class fluxgate high-precision leakage current sensor

Used for high-precision measurement of DC, AC, and pulse leakage current, with optimal measurement accuracy up to 0.2% .

 

 

Features

application

Advantages

standard

l   High-precision zero-flux closed-loop control

l   Strong resistance to electromagnetic interference

l   LED status display

l   Full-range automatic switching technology

l   Wide temperature range design, operating temperature from -40 to 90

l   Smart grid, new energy

l   Industrial manufacturing, converters, inverters

l   Aerospace , satellites, rockets

l   Verification and Calibration Equipment

l   High-speed trains, subways, and trolleybuses

l   Original and secondary border isolation measurement

l   0.2% measurement accuracy

l   Excellent linearity and extremely low temperature drift.

l   Wide bandwidth and low response time

l   Professional magnetoelectric design, strong resistance to electromagnetic interference

l   Excellent testing capabilities

l   IEC 61010-1

l   IEC 61000-6-2:2016

l   IEC 61000-6-3:2006

l   IEC 61010-2-030:2017

l   IEC 60112

 

 

 

 

Environmental and mechanical properties

project

parameter

Ambient operating temperature / T A

-40 to 90

Storage ambient temperature / T S

-40 to 90

Relative humidity /RH

20%RH to 80%RH

mechanical shock protection level

IP54

 

Insulation properties

project

Test conditions

parameter

Isolation voltage / V d

50Hz, 1min

5kV

Transient isolation withstand voltage / V w

50us

10kV

Creepage distance / d Cp

 

11mm

Electrical clearance distance / d Ci

 

11mm

Compared to the tracking index / CTI

IEC-60112

275V

 

Electrical parameters

project

Test conditions

Minimum value

nominal value

Maximum value

unit

Operating voltage / V C

±14.2

±15

±15.8

V

Static power consumption current / I PWR

Primary rated current

±30

mA

Accuracy / X G

Input DC, 25±10ºC

0.2

%

Linearity / εL

0.2

%

Dynamic response time / t r

di/dt = 100 A/ μs , rising to 90% IPN

2

m s

Rate of change of current / di / dt

2 00

A/ μs

Bandwidth (-3dB)/F

0

1 00

kHz

 

Selection list

Serial Number

Product Model

Primary rated current

Overload capacity

Output signal

Installation method and dimensions

1

FTS.FGR001

±10mA

±20mA

±0.05V

Disc installation

Figure 1

2

FTS.FGR002

±20mA

±40mA

±0.1V

3

FTS.FGR01

±100mA

±200mA

±0.5V

4

FTS.FGR02

±200mA

±400mA

±1V

5

FTS.FGR05

±500mA

±1A

±2.5V

6

FTS.FGR1

±1A

±2A

±5V

7

FTS.FGR5

±5A

±10A

±5V

8

FTS.FGR10

±10A

±20A

±5V

 Note: Please contact customer service for other needs;